A Leap Forward in Dryer Technology
Technical specifications for AC 200-630 VSD |
|||||||
Specifications ¯ |
Units |
AC200 VSD |
AC300 VSD |
AC400 VSD |
AC450 VSD |
AC550 VSD |
AC630 VSD |
Maximum conditions at full flow ambient (Inlet) temp |
°C |
46 (60) |
46 (60) |
46 (60) |
46 (60) |
46 (60) |
46 (60) |
Inlet flow for pressure dew point (PDP) of 3°C / 37.4°F |
l/s |
100 |
140 |
180 |
220 |
260 |
300 |
cfm |
212 |
297 |
381 |
466 |
551 |
636 |
|
m3/hr |
360 |
500 |
650 |
790 |
940 |
1080 |
|
Pressure drop at full flow |
bar |
0.16 2.3 |
0.11 1.6 |
0.18 2.6 |
0.14 2 |
0.1 1.5 |
0.18 2.6 |
psi |
|||||||
Power consumption |
kW |
0.66 |
1.04 |
1.54 |
1.77 |
1.9 |
2.64 |
hp |
0.90 |
1.41 |
2.09 |
2.41 |
2.58 |
3.59 |
|
Max. working pressure |
bar |
14.5 210 |
14.5 210 |
14.5 210 |
14.5 210 |
14.5 210 |
14.5 210 |
psi |
|||||||
Compressed air connections (NPT for UL version) |
|
G 1 ½” F |
G 2” F |
G 2” F |
G 2 1/2” F |
G 2 1/2” F |
G 2 1/2” F |
|
mm |
805 |
805 |
805 |
805 |
805 |
805 |
|
inch |
31.69 |
31.69 |
31.69 |
31.69 |
31.69 |
31.69 |
Dimensions |
mm |
962 |
962 |
962 |
962 |
962 |
962 |
inch |
37.87 |
37.87 |
37.87 |
37.87 |
37.87 |
37.87 |
|
|
mm |
1040 |
1040 |
1040 |
1040 |
1040 |
1040 |
|
inch |
41 |
41 |
41 |
41 |
41 |
41 |
Weight |
kg |
130 |
134 |
134 |
143 |
150 |
165 |
lbs |
287 |
295 |
295 |
315 |
331 |
364 |